Glossary

Every acronym + term used in Power Atlas, with section reference

A: Acronyms A-Z. Click a letter to jump.

A B C D E F G H I K L M N O P R S T U V W X Z

A

AC
Alternating Current. Power that reverses direction at the line frequency (60 Hz in US). §01
AC (cable)
Armored Cable (BX). Older commercial wiring with conductors in flexible armor (no separate ground). NEC 320. §07
AFB
Arc Flash Boundary. Distance at which incident energy drops to 1.2 cal/cm² (2nd-degree burn threshold). §18
AFCI
Arc-Fault Circuit Interrupter. Detects arcing faults on branch circuits. NEC 210.12. Required in dwelling bedrooms (and more). §04
AFE
Active Front End. VFD with active rectifier — produces < 5% THDi vs 30%+ for standard 6-pulse. §14, §15
AGM
Absorbent Glass Mat. A type of VRLA battery construction. §20
AHJ
Authority Having Jurisdiction. The person/office responsible for enforcing electrical code (typically city/county building dept). §30
AIC
Amperes Interrupting Capacity. The maximum fault current a device (breaker/fuse) can safely interrupt. §12
ANSI
American National Standards Institute. Source of voltage standards (C84.1) and protective device numbering (C37.2). §01, §17, §32
Apparent power (S)
Total power flowing in a circuit, including reactive component. Measured in VA / kVA. Conductors carry S, not just P. §01
ASHRAE
American Society of Heating, Refrigerating + Air-Conditioning Engineers. ASHRAE 90.1 = commercial energy code. ASHRAE 90.4 = data center energy. §31
ATS
Automatic Transfer Switch. Device that transfers load between utility and standby power source. §19
AWG
American Wire Gauge. Conductor size. Smaller number = larger conductor. §04, §07

B

BIL
Basic Impulse Level. Equipment's withstand voltage rating for lightning impulses. §09, §23
BMS
Building Management System (HVAC + lighting), or Battery Management System (Li-ion ESS). Context-dependent. §20, §25
Bonding jumper
Conductor that ensures electrical continuity between metallic parts. NEC 250. §13
Branch circuit
Conductors between final OCPD and outlet/equipment. NEC 210, 430. §04
BTU/hr
British Thermal Unit per hour. Heat unit. 1 kW = 3,412 BTU/hr. §01
Bus
Conductor that distributes power to multiple connections. Switchgear bus, transformer bus, etc. §05
Busway
Factory-built bus bars in metal enclosure. NEC 368. §08

C

Cable tray
Open support system for cables. NEC 392. §08
cal/cm²
Calories per square centimeter. Unit of incident energy in arc flash. §18
CB
Circuit Breaker. Reusable overcurrent device. §11
Class I/II/III
Hazardous location classification: gas (I), dust (II), fibers (III). NEC 500. §21
CMR
Communications Riser cable. NEC 800. §32
Code letter
Motor nameplate letter (A-V) indicating locked-rotor kVA per HP. §14
COPS
Critical Operations Power Systems. NEC 708. Highest-tier emergency. §19
CRAH
Computer Room Air Handler. Cools data center IT halls. §14
CSI
Construction Specifications Institute. MasterFormat division system. Division 26 = Electrical. §28
CT
Current Transformer. Steps down current for metering or protection. §17, §22
CWP
Condenser Water Pump. Pumps water to/from cooling tower. §14

D

DC
Direct Current. §20
DCFC
DC Fast Charging. Level 3 EV charging (50-350+ kW). §26
Demand factor
Ratio of max demand to total connected load. Always ≤ 1.0. NEC 220. §03
DCFC
DC Fast Charging — see also Level 3. §26
Diversity factor
Ratio of sum of individual peaks to system peak. Always ≥ 1.0. §03
Δ (delta)
Three-phase winding configuration where windings form a triangle. No neutral. §09
DOL
Direct-On-Line. Motor starting method — connects motor directly to line. 6-8× FLA inrush. §14
DR
Demand Response. Utility program paying for load reduction during peaks. §27
DRC
Daylight Responsive Controls. Required by ASHRAE 90.1 within 15 ft of windows. §31
Drawout breaker
CB removable from cubicle for service. Common in switchgear. §05, §22

E

EGC
Equipment Grounding Conductor. Bonds equipment metal to ground. NEC 250.122. §13
ELC
Electrical Loss Component (ASHRAE 90.4 metric). §31
EMT
Electrical Metallic Tubing. Thin-wall conduit. NEC 358. §04, §07
EPR
Ethylene Propylene Rubber. Premium MV cable insulation. §07
ESS
Energy Storage System. Battery (or other) backup. NEC 706, NFPA 855. §25
EV
Electric Vehicle. §26
EVEMS
EV Energy Management System. Allows demand reduction via load sharing. NEC 625.42. §26
EVSE
EV Supply Equipment. The "charger" (actual battery charger is in the car). NEC 625. §26

F

FLA
Full Load Amperes. Motor current at rated mechanical output. §01, §04
FLC
Full Load Current. NEC table value (NEC 430.247-250). Use FLC, not FLA, for NEC sizing. §04, §14
FOIT/FOUT
Flash Of Invisible/Unstyled Text. Web typography artifact (off-topic but appeared in identity). N/A
Fuse
Sacrificial overcurrent device. Cleared by element melting. §11

G

GEC
Grounding Electrode Conductor. From service neutral to ground electrode. NEC 250.66. §13
GFCI
Ground-Fault Circuit Interrupter. Personnel protection (5 mA). NEC 210.8. §13
GFP / GFPE
Ground Fault Protection of Equipment. NEC 230.95 — required at 480V services ≥ 1000A. 1,200A pickup max. §13
GIS
Gas-Insulated Switchgear. SF6 gas-insulated, compact. §22
GFP
(See GFP / GFPE.)
Group LOTO
Multiple workers each apply own lock to a multi-lock hasp. §29

H

Harmonic
Frequency component above the fundamental (60 Hz). 5th harmonic = 300 Hz. Generated by nonlinear loads. §15
HP
Horsepower. Mechanical output rating. 1 HP = 0.746 kW. §01, §14
HRG
High-Resistance Grounded. Industrial grounding scheme limiting ground fault to ~ 5 A. §13

I

I (current)
Electrical current, measured in Amperes (A). Color-coded red in Power Atlas formulas. §01
ICCB
Insulated-Case Circuit Breaker. Higher-tier than MCCB. §12
IECC
International Energy Conservation Code. Building energy code. §31
IEEE
Institute of Electrical and Electronics Engineers. Issues color books, IEEE 1584, IEEE 519, etc. §32
IFC
Issued for Construction. Drawing version released for construction. §28
Incident energy
Arc flash energy at working distance, measured in cal/cm². 1.2 cal/cm² = 2nd-degree burn threshold. §18
IS
Intrinsically Safe. Hazardous location protection method — energy too low to ignite. §21
IT
Information Technology. Server load in data centers. §02

K

K-factor transformer
Transformer rated for harmonic loads. K-13 = data center standard. K-4 = light harmonics. §09, §15
kVA
Kilovolt-Ampere. Apparent power unit. 1000 VA. §01
kVAR
Kilovolt-Ampere Reactive. Reactive power unit. §01, §15
kW
Kilowatt. Real power unit. 1000 W. §01

L

L1, L2, L3
Line conductors of a 3-phase system (also Phase A, B, C). §01
L1, L2 charging
EV charging levels. L1 = 120V. L2 = 208/240V. §26
LFP
Lithium Iron Phosphate. Safer Li-ion chemistry. §20
LOTO
Lockout/Tagout. Energy isolation procedure. NFPA 70E + OSHA 1910.147. §29
LPL
Lightning Protection Level. IEC 62305 risk classification. §23
LPD
Lighting Power Density. W/sq ft limit per ASHRAE 90.1. §31
LRA
Locked-Rotor Amperes. Motor starting current (6-8× FLA). §14
LRkVA/HP
Locked-Rotor kVA per HP. Determined by motor Code Letter. §14
LSI / LSIG
Long-time / Short-time / Instantaneous (+ Ground). Adjustable trip settings on electronic CBs. §11
LV
Low Voltage (≤ 600V per NEC 110.2). §02

M

MBJ
Main Bonding Jumper. Joins service neutral to ground at service equipment. ONE per service. NEC 250.28. §13
MC
Metal-Clad cable. Conductors in metal armor. NEC 330. §07
MCA
Minimum Circuit Ampacity. Sets the wire size. For motors: 1.25 × FLC (NEC 430.22). §04
MCB
Main Circuit Breaker. Panel's main disconnect. §05
MCCB
Molded-Case Circuit Breaker. Standard panelboard breaker. §12
MCC
Motor Control Center. Modular cabinet of motor starters. §14
MCOV
Maximum Continuous Operating Voltage (SPDs). Sustained voltage SPD can withstand without operation. §24
MEL
Master Equipment List. Document of all loads requiring power. From other disciplines to electrical. §02
MLO
Main Lug Only. Panel without integral main breaker — fed protected from upstream. §05
MLC
Mechanical Load Component (ASHRAE 90.4 metric). §31
MOV
Metal Oxide Varistor. SPD technology. Wears out with each surge. §24
MOCP
Maximum Overcurrent Protection. Caps the breaker size. NEC 430.52 (motors). §04
MV
Medium Voltage (1 - 35 kV). NEC 110.2. §02
MVA
Megavolt-Ampere. 1,000 kVA. §01, §12
MVA method
Fault current calculation method using MVA additions. §12

N

NEC
National Electrical Code (NFPA 70). The electrical installation standard. Updated every 3 years. §32
NEMA
National Electrical Manufacturers Association. Sets equipment standards (enclosures, motor frames, starter sizes). §14
NFPA
National Fire Protection Association. Issues NEC, NFPA 70E, NFPA 110, NFPA 780, NFPA 855. §32
NM-B
Non-Metallic sheathed cable type B (Romex). Residential interior. NEC 334. §07
NMC
Nickel Manganese Cobalt. Higher-energy Li-ion chemistry. Higher thermal runaway risk than LFP. §20

O

OCPD
OverCurrent Protective Device (breaker or fuse). NEC 240. §11
ODP
Open Drip-Proof motor enclosure. §14
ONAN
Oil-immersed Natural Air Natural cooling (transformer). §09
OFCI
Owner-Furnished, Contractor-Installed. Common in DC industry. §28
OSHA
Occupational Safety + Health Administration. Federal workplace safety. 29 CFR 1910 + 1926. §32

P

P (real power)
Real (active) power, measured in Watts (W). Color-coded green in Power Atlas. §01
PCC
Point of Common Coupling. Boundary between user and utility. IEEE 519 limits apply here. §15
PDU
Power Distribution Unit. Data center: 480 → 415Y/240V step-down + integral panel. §05
PF
Power Factor. cos θ = P/S. 1.0 = pure resistive; 0.8 = lagging inductive. §01, §15
PFC
Power Factor Correction. Capacitor banks (or inverter-based) to bring PF closer to 1.0. §15
PMS
Power Management System. Centralized controller for complex emergency systems. §27
PMSM
Permanent Magnet Synchronous Motor. Modern HVAC + EV motor. §14
PPE
Personal Protective Equipment. NFPA 70E categorizes by arc flash incident energy. §18
PT / VT
Potential / Voltage Transformer. Steps down voltage for metering or protection. §17, §22
Per-unit
Quantities normalized to a base value. Used in fault and load flow analysis. §01, §12
PUE
Power Usage Effectiveness. Total facility power / IT power. 1.0 = perfect, 2.0 = inefficient. §31
PV
Photovoltaic. Solar electricity. NEC 690. §25
PWM
Pulse Width Modulation. VFD output technique. §14

R

R (resistance)
Electrical resistance, measured in Ohms (Ω). §01
Rapid shutdown
NEC 690.12 — PV array DC voltage must drop to safe level within 30 sec of activation. §25
RCM
Reverse Current Monitor. Some utility intertie protection. §25
RFI
Request for Information. Contractor question requiring formal engineer response. §28
RMC
Rigid Metal Conduit. Heaviest gauge raceway. NEC 344. §07
RMS
Root Mean Square. Equivalent DC heating value of an AC waveform. Standard AC measurement. §12
RPP
Remote Power Panel. Data center row-level branch panel, fed from PDU. §05

S

S (apparent power)
Apparent (total) power, measured in VA / kVA. Color-coded purple in Power Atlas. S² = P² + Q². §01
SAD
Silicon Avalanche Diode. SPD technology — faster + tighter than MOV. §24
SCC
Short-Circuit Current. Same as available fault current. §12
SCCR
Short-Circuit Current Rating. UL 508A rating for industrial control panels. §05
SCR
Silicon Controlled Rectifier (semiconductor) OR Short Circuit Ratio (IEEE 519). Context-dependent. §14, §15
SE / SER
Service Entrance cable. Residential. NEC 338. §07
SF (motor)
Service Factor. Multiplier on motor's continuous overload rating. 1.0 or 1.15 typical. §14
SFP
Sound-Field Particles (acronym sometimes used in arc flash for plasma). N/A in Power Atlas.
SLD
Single-Line Diagram. Schematic showing 3-phase system as single lines. The system map. §02
Soft Starter
Reduced-voltage motor starter using SCRs. Ramps voltage on start. §14
SPD
Surge Protective Device. NEC 285. §24
SWGR
Switchgear. Free-standing switching equipment, drawout breakers. §05

T

T-code
Hazardous location temperature code. T1 (450°C max) - T6 (85°C max). Equipment T-code < gas auto-ignition. §21
Tap conductor
Smaller conductor branched from larger feeder. NEC 240.21 special rules. §06
TC / TC-ER
Tray Cable / Tray Cable Exposed-Run rated. NEC 336. §07, §08
TCC
Time-Current Curve. Plots OCPD trip time vs current on log-log axes. Used for coordination studies. §11, §17
TDD
Total Demand Distortion. % distortion vs maximum demand current. IEEE 519 uses TDD. §15
TEFC
Totally Enclosed Fan-Cooled. Most common motor enclosure. §14
THD
Total Harmonic Distortion. % distortion vs fundamental. §15
THDi
Total Harmonic Distortion of current. §15
THHN
Thermoplastic, Heat-resistant (90°C dry only), Nylon-jacketed. NEC 310. §07
THWN-2
Thermoplastic, Heat- + Wet-resistant (90°C wet/dry), Nylon. The default modern conductor. §07
Tier (data center)
Uptime Institute classification: Tier I (basic) — Tier IV (fault tolerant). Atlas DC1 = Tier III equivalent. §02
TPG
Temporary Protective Ground. Used during MV/HV LOTO. §29
Triplens
3rd, 9th, 15th harmonics — add in neutral instead of cancel. §15
TX
Transformer (abbreviation in SLDs). §02, §09

U

UF / UF-B
Underground Feeder cable. Direct-burial residential. NEC 340. §07
UL
Underwriters Laboratories. Independent product testing. UL 489 (CBs), UL 508A (industrial control panels), UL 1741 (inverters), etc. §32
UPS
Uninterruptible Power Supply. Battery-backed power, no transfer time (online double-conversion type). §19
USE-2
Underground Service Entrance, 90°C wet/dry. NEC 338. §07

V

V (voltage)
Voltage, measured in Volts. Color-coded blue in Power Atlas. §01
VAR
Volt-Ampere Reactive. Unit of reactive power. §01, §15
VLL
Line-to-Line voltage. Between two phase conductors. §01
VLN
Line-to-Neutral voltage. Between phase and neutral. VLL = √3 × VLN. §01
VFD
Variable Frequency Drive. AC motor speed controller. §14
VPR
Voltage Protection Rating (SPDs). What voltage gets through during a surge. Lower is better. §24
VRLA
Valve-Regulated Lead-Acid. Sealed batteries common in UPS. §20

W

W
Watt. Real power unit. §01
Wireway
Sheet metal trough with hinged cover for conductor support. NEC 376. §08
Working space
NEC 110.26 — clearance required around electrical equipment. Most-cited rule. §30

X

X (reactance)
Inductive (XL) or capacitive (XC) reactance. Imaginary component of impedance. §01
X/R ratio
System reactance/resistance. Higher = more asymmetric fault current. §12
XFMR / TX
Transformer abbreviations. §09
XHHW-2
XLPE insulation, Heat- + Wet-rated 90°C wet/dry. Premium conductor. NEC 310. §07
XLPE
Cross-Linked Polyethylene insulation. Tougher than PVC. §07
XP
Explosion-Proof (Class I Div 1 motor enclosure). §21

Z

Z (impedance)
Total opposition to AC current. Z = R + jX. Color-coded iron/dark in Power Atlas. §01
%Z
Per-unit transformer impedance. Low %Z = high downstream fault current. §09
Zone (haz loc)
IEC system for hazardous locations. Zone 0 / 1 / 2 (gas), Zone 20 / 21 / 22 (dust). §21
ZSI
Zone-Selective Interlocking. Modern CB technique for selective coordination at full speed. §11, §18

Glossary v1.0 · ~ 200 entries · cross-referenced to sections