A: Acronyms A-Z. Click a letter to jump.
A
- AC
- Alternating Current. Power that reverses direction at the line frequency (60 Hz in US). §01
- AC (cable)
- Armored Cable (BX). Older commercial wiring with conductors in flexible armor (no separate ground). NEC 320. §07
- AFB
- Arc Flash Boundary. Distance at which incident energy drops to 1.2 cal/cm² (2nd-degree burn threshold). §18
- AFCI
- Arc-Fault Circuit Interrupter. Detects arcing faults on branch circuits. NEC 210.12. Required in dwelling bedrooms (and more). §04
- AFE
- Active Front End. VFD with active rectifier — produces < 5% THDi vs 30%+ for standard 6-pulse. §14, §15
- AGM
- Absorbent Glass Mat. A type of VRLA battery construction. §20
- AHJ
- Authority Having Jurisdiction. The person/office responsible for enforcing electrical code (typically city/county building dept). §30
- AIC
- Amperes Interrupting Capacity. The maximum fault current a device (breaker/fuse) can safely interrupt. §12
- ANSI
- American National Standards Institute. Source of voltage standards (C84.1) and protective device numbering (C37.2). §01, §17, §32
- Apparent power (S)
- Total power flowing in a circuit, including reactive component. Measured in VA / kVA. Conductors carry S, not just P. §01
- ASHRAE
- American Society of Heating, Refrigerating + Air-Conditioning Engineers. ASHRAE 90.1 = commercial energy code. ASHRAE 90.4 = data center energy. §31
- ATS
- Automatic Transfer Switch. Device that transfers load between utility and standby power source. §19
- AWG
- American Wire Gauge. Conductor size. Smaller number = larger conductor. §04, §07
B
- BIL
- Basic Impulse Level. Equipment's withstand voltage rating for lightning impulses. §09, §23
- BMS
- Building Management System (HVAC + lighting), or Battery Management System (Li-ion ESS). Context-dependent. §20, §25
- Bonding jumper
- Conductor that ensures electrical continuity between metallic parts. NEC 250. §13
- Branch circuit
- Conductors between final OCPD and outlet/equipment. NEC 210, 430. §04
- BTU/hr
- British Thermal Unit per hour. Heat unit. 1 kW = 3,412 BTU/hr. §01
- Bus
- Conductor that distributes power to multiple connections. Switchgear bus, transformer bus, etc. §05
- Busway
- Factory-built bus bars in metal enclosure. NEC 368. §08
C
- Cable tray
- Open support system for cables. NEC 392. §08
- cal/cm²
- Calories per square centimeter. Unit of incident energy in arc flash. §18
- CB
- Circuit Breaker. Reusable overcurrent device. §11
- Class I/II/III
- Hazardous location classification: gas (I), dust (II), fibers (III). NEC 500. §21
- CMR
- Communications Riser cable. NEC 800. §32
- Code letter
- Motor nameplate letter (A-V) indicating locked-rotor kVA per HP. §14
- COPS
- Critical Operations Power Systems. NEC 708. Highest-tier emergency. §19
- CRAH
- Computer Room Air Handler. Cools data center IT halls. §14
- CSI
- Construction Specifications Institute. MasterFormat division system. Division 26 = Electrical. §28
- CT
- Current Transformer. Steps down current for metering or protection. §17, §22
- CWP
- Condenser Water Pump. Pumps water to/from cooling tower. §14
D
- DC
- Direct Current. §20
- DCFC
- DC Fast Charging. Level 3 EV charging (50-350+ kW). §26
- Demand factor
- Ratio of max demand to total connected load. Always ≤ 1.0. NEC 220. §03
- DCFC
- DC Fast Charging — see also Level 3. §26
- Diversity factor
- Ratio of sum of individual peaks to system peak. Always ≥ 1.0. §03
- Δ (delta)
- Three-phase winding configuration where windings form a triangle. No neutral. §09
- DOL
- Direct-On-Line. Motor starting method — connects motor directly to line. 6-8× FLA inrush. §14
- DR
- Demand Response. Utility program paying for load reduction during peaks. §27
- DRC
- Daylight Responsive Controls. Required by ASHRAE 90.1 within 15 ft of windows. §31
- Drawout breaker
- CB removable from cubicle for service. Common in switchgear. §05, §22
E
- EGC
- Equipment Grounding Conductor. Bonds equipment metal to ground. NEC 250.122. §13
- ELC
- Electrical Loss Component (ASHRAE 90.4 metric). §31
- EMT
- Electrical Metallic Tubing. Thin-wall conduit. NEC 358. §04, §07
- EPR
- Ethylene Propylene Rubber. Premium MV cable insulation. §07
- ESS
- Energy Storage System. Battery (or other) backup. NEC 706, NFPA 855. §25
- EV
- Electric Vehicle. §26
- EVEMS
- EV Energy Management System. Allows demand reduction via load sharing. NEC 625.42. §26
- EVSE
- EV Supply Equipment. The "charger" (actual battery charger is in the car). NEC 625. §26
F
- FLA
- Full Load Amperes. Motor current at rated mechanical output. §01, §04
- FLC
- Full Load Current. NEC table value (NEC 430.247-250). Use FLC, not FLA, for NEC sizing. §04, §14
- FOIT/FOUT
- Flash Of Invisible/Unstyled Text. Web typography artifact (off-topic but appeared in identity). N/A
- Fuse
- Sacrificial overcurrent device. Cleared by element melting. §11
G
- GEC
- Grounding Electrode Conductor. From service neutral to ground electrode. NEC 250.66. §13
- GFCI
- Ground-Fault Circuit Interrupter. Personnel protection (5 mA). NEC 210.8. §13
- GFP / GFPE
- Ground Fault Protection of Equipment. NEC 230.95 — required at 480V services ≥ 1000A. 1,200A pickup max. §13
- GIS
- Gas-Insulated Switchgear. SF6 gas-insulated, compact. §22
- GFP
- (See GFP / GFPE.)
- Group LOTO
- Multiple workers each apply own lock to a multi-lock hasp. §29
H
- Harmonic
- Frequency component above the fundamental (60 Hz). 5th harmonic = 300 Hz. Generated by nonlinear loads. §15
- HP
- Horsepower. Mechanical output rating. 1 HP = 0.746 kW. §01, §14
- HRG
- High-Resistance Grounded. Industrial grounding scheme limiting ground fault to ~ 5 A. §13
I
- I (current)
- Electrical current, measured in Amperes (A). Color-coded red in Power Atlas formulas. §01
- ICCB
- Insulated-Case Circuit Breaker. Higher-tier than MCCB. §12
- IECC
- International Energy Conservation Code. Building energy code. §31
- IEEE
- Institute of Electrical and Electronics Engineers. Issues color books, IEEE 1584, IEEE 519, etc. §32
- IFC
- Issued for Construction. Drawing version released for construction. §28
- Incident energy
- Arc flash energy at working distance, measured in cal/cm². 1.2 cal/cm² = 2nd-degree burn threshold. §18
- IS
- Intrinsically Safe. Hazardous location protection method — energy too low to ignite. §21
- IT
- Information Technology. Server load in data centers. §02
K
- K-factor transformer
- Transformer rated for harmonic loads. K-13 = data center standard. K-4 = light harmonics. §09, §15
- kVA
- Kilovolt-Ampere. Apparent power unit. 1000 VA. §01
- kVAR
- Kilovolt-Ampere Reactive. Reactive power unit. §01, §15
- kW
- Kilowatt. Real power unit. 1000 W. §01
L
- L1, L2, L3
- Line conductors of a 3-phase system (also Phase A, B, C). §01
- L1, L2 charging
- EV charging levels. L1 = 120V. L2 = 208/240V. §26
- LFP
- Lithium Iron Phosphate. Safer Li-ion chemistry. §20
- LOTO
- Lockout/Tagout. Energy isolation procedure. NFPA 70E + OSHA 1910.147. §29
- LPL
- Lightning Protection Level. IEC 62305 risk classification. §23
- LPD
- Lighting Power Density. W/sq ft limit per ASHRAE 90.1. §31
- LRA
- Locked-Rotor Amperes. Motor starting current (6-8× FLA). §14
- LRkVA/HP
- Locked-Rotor kVA per HP. Determined by motor Code Letter. §14
- LSI / LSIG
- Long-time / Short-time / Instantaneous (+ Ground). Adjustable trip settings on electronic CBs. §11
- LV
- Low Voltage (≤ 600V per NEC 110.2). §02
M
- MBJ
- Main Bonding Jumper. Joins service neutral to ground at service equipment. ONE per service. NEC 250.28. §13
- MC
- Metal-Clad cable. Conductors in metal armor. NEC 330. §07
- MCA
- Minimum Circuit Ampacity. Sets the wire size. For motors: 1.25 × FLC (NEC 430.22). §04
- MCB
- Main Circuit Breaker. Panel's main disconnect. §05
- MCCB
- Molded-Case Circuit Breaker. Standard panelboard breaker. §12
- MCC
- Motor Control Center. Modular cabinet of motor starters. §14
- MCOV
- Maximum Continuous Operating Voltage (SPDs). Sustained voltage SPD can withstand without operation. §24
- MEL
- Master Equipment List. Document of all loads requiring power. From other disciplines to electrical. §02
- MLO
- Main Lug Only. Panel without integral main breaker — fed protected from upstream. §05
- MLC
- Mechanical Load Component (ASHRAE 90.4 metric). §31
- MOV
- Metal Oxide Varistor. SPD technology. Wears out with each surge. §24
- MOCP
- Maximum Overcurrent Protection. Caps the breaker size. NEC 430.52 (motors). §04
- MV
- Medium Voltage (1 - 35 kV). NEC 110.2. §02
- MVA
- Megavolt-Ampere. 1,000 kVA. §01, §12
- MVA method
- Fault current calculation method using MVA additions. §12
N
- NEC
- National Electrical Code (NFPA 70). The electrical installation standard. Updated every 3 years. §32
- NEMA
- National Electrical Manufacturers Association. Sets equipment standards (enclosures, motor frames, starter sizes). §14
- NFPA
- National Fire Protection Association. Issues NEC, NFPA 70E, NFPA 110, NFPA 780, NFPA 855. §32
- NM-B
- Non-Metallic sheathed cable type B (Romex). Residential interior. NEC 334. §07
- NMC
- Nickel Manganese Cobalt. Higher-energy Li-ion chemistry. Higher thermal runaway risk than LFP. §20
O
- OCPD
- OverCurrent Protective Device (breaker or fuse). NEC 240. §11
- ODP
- Open Drip-Proof motor enclosure. §14
- ONAN
- Oil-immersed Natural Air Natural cooling (transformer). §09
- OFCI
- Owner-Furnished, Contractor-Installed. Common in DC industry. §28
- OSHA
- Occupational Safety + Health Administration. Federal workplace safety. 29 CFR 1910 + 1926. §32
P
- P (real power)
- Real (active) power, measured in Watts (W). Color-coded green in Power Atlas. §01
- PCC
- Point of Common Coupling. Boundary between user and utility. IEEE 519 limits apply here. §15
- PDU
- Power Distribution Unit. Data center: 480 → 415Y/240V step-down + integral panel. §05
- PF
- Power Factor. cos θ = P/S. 1.0 = pure resistive; 0.8 = lagging inductive. §01, §15
- PFC
- Power Factor Correction. Capacitor banks (or inverter-based) to bring PF closer to 1.0. §15
- PMS
- Power Management System. Centralized controller for complex emergency systems. §27
- PMSM
- Permanent Magnet Synchronous Motor. Modern HVAC + EV motor. §14
- PPE
- Personal Protective Equipment. NFPA 70E categorizes by arc flash incident energy. §18
- PT / VT
- Potential / Voltage Transformer. Steps down voltage for metering or protection. §17, §22
- Per-unit
- Quantities normalized to a base value. Used in fault and load flow analysis. §01, §12
- PUE
- Power Usage Effectiveness. Total facility power / IT power. 1.0 = perfect, 2.0 = inefficient. §31
- PV
- Photovoltaic. Solar electricity. NEC 690. §25
- PWM
- Pulse Width Modulation. VFD output technique. §14
R
- R (resistance)
- Electrical resistance, measured in Ohms (Ω). §01
- Rapid shutdown
- NEC 690.12 — PV array DC voltage must drop to safe level within 30 sec of activation. §25
- RCM
- Reverse Current Monitor. Some utility intertie protection. §25
- RFI
- Request for Information. Contractor question requiring formal engineer response. §28
- RMC
- Rigid Metal Conduit. Heaviest gauge raceway. NEC 344. §07
- RMS
- Root Mean Square. Equivalent DC heating value of an AC waveform. Standard AC measurement. §12
- RPP
- Remote Power Panel. Data center row-level branch panel, fed from PDU. §05
S
- S (apparent power)
- Apparent (total) power, measured in VA / kVA. Color-coded purple in Power Atlas. S² = P² + Q². §01
- SAD
- Silicon Avalanche Diode. SPD technology — faster + tighter than MOV. §24
- SCC
- Short-Circuit Current. Same as available fault current. §12
- SCCR
- Short-Circuit Current Rating. UL 508A rating for industrial control panels. §05
- SCR
- Silicon Controlled Rectifier (semiconductor) OR Short Circuit Ratio (IEEE 519). Context-dependent. §14, §15
- SE / SER
- Service Entrance cable. Residential. NEC 338. §07
- SF (motor)
- Service Factor. Multiplier on motor's continuous overload rating. 1.0 or 1.15 typical. §14
- SFP
- Sound-Field Particles (acronym sometimes used in arc flash for plasma). N/A in Power Atlas.
- SLD
- Single-Line Diagram. Schematic showing 3-phase system as single lines. The system map. §02
- Soft Starter
- Reduced-voltage motor starter using SCRs. Ramps voltage on start. §14
- SPD
- Surge Protective Device. NEC 285. §24
- SWGR
- Switchgear. Free-standing switching equipment, drawout breakers. §05
T
- T-code
- Hazardous location temperature code. T1 (450°C max) - T6 (85°C max). Equipment T-code < gas auto-ignition. §21
- Tap conductor
- Smaller conductor branched from larger feeder. NEC 240.21 special rules. §06
- TC / TC-ER
- Tray Cable / Tray Cable Exposed-Run rated. NEC 336. §07, §08
- TCC
- Time-Current Curve. Plots OCPD trip time vs current on log-log axes. Used for coordination studies. §11, §17
- TDD
- Total Demand Distortion. % distortion vs maximum demand current. IEEE 519 uses TDD. §15
- TEFC
- Totally Enclosed Fan-Cooled. Most common motor enclosure. §14
- THD
- Total Harmonic Distortion. % distortion vs fundamental. §15
- THDi
- Total Harmonic Distortion of current. §15
- THHN
- Thermoplastic, Heat-resistant (90°C dry only), Nylon-jacketed. NEC 310. §07
- THWN-2
- Thermoplastic, Heat- + Wet-resistant (90°C wet/dry), Nylon. The default modern conductor. §07
- Tier (data center)
- Uptime Institute classification: Tier I (basic) — Tier IV (fault tolerant). Atlas DC1 = Tier III equivalent. §02
- TPG
- Temporary Protective Ground. Used during MV/HV LOTO. §29
- Triplens
- 3rd, 9th, 15th harmonics — add in neutral instead of cancel. §15
- TX
- Transformer (abbreviation in SLDs). §02, §09
U
- UF / UF-B
- Underground Feeder cable. Direct-burial residential. NEC 340. §07
- UL
- Underwriters Laboratories. Independent product testing. UL 489 (CBs), UL 508A (industrial control panels), UL 1741 (inverters), etc. §32
- UPS
- Uninterruptible Power Supply. Battery-backed power, no transfer time (online double-conversion type). §19
- USE-2
- Underground Service Entrance, 90°C wet/dry. NEC 338. §07
V
- V (voltage)
- Voltage, measured in Volts. Color-coded blue in Power Atlas. §01
- VAR
- Volt-Ampere Reactive. Unit of reactive power. §01, §15
- VLL
- Line-to-Line voltage. Between two phase conductors. §01
- VLN
- Line-to-Neutral voltage. Between phase and neutral. VLL = √3 × VLN. §01
- VFD
- Variable Frequency Drive. AC motor speed controller. §14
- VPR
- Voltage Protection Rating (SPDs). What voltage gets through during a surge. Lower is better. §24
- VRLA
- Valve-Regulated Lead-Acid. Sealed batteries common in UPS. §20
W
- W
- Watt. Real power unit. §01
- Wireway
- Sheet metal trough with hinged cover for conductor support. NEC 376. §08
- Working space
- NEC 110.26 — clearance required around electrical equipment. Most-cited rule. §30
X
- X (reactance)
- Inductive (XL) or capacitive (XC) reactance. Imaginary component of impedance. §01
- X/R ratio
- System reactance/resistance. Higher = more asymmetric fault current. §12
- XFMR / TX
- Transformer abbreviations. §09
- XHHW-2
- XLPE insulation, Heat- + Wet-rated 90°C wet/dry. Premium conductor. NEC 310. §07
- XLPE
- Cross-Linked Polyethylene insulation. Tougher than PVC. §07
- XP
- Explosion-Proof (Class I Div 1 motor enclosure). §21
Z
- Z (impedance)
- Total opposition to AC current. Z = R + jX. Color-coded iron/dark in Power Atlas. §01
- %Z
- Per-unit transformer impedance. Low %Z = high downstream fault current. §09
- Zone (haz loc)
- IEC system for hazardous locations. Zone 0 / 1 / 2 (gas), Zone 20 / 21 / 22 (dust). §21
- ZSI
- Zone-Selective Interlocking. Modern CB technique for selective coordination at full speed. §11, §18
Glossary v1.0 · ~ 200 entries · cross-referenced to sections