Transformers
Every voltage transition in your system has a transformer behind it. Sizing comes from the load study; %Z determines fault current downstream; the winding configuration determines grounding rules. Get all three from the cutsheet.
The Three Numbers Every Transformer Cutsheet Has
Sizing is from the load study (kVA). %Z determines downstream fault current. The winding configuration determines grounding rules. Get all three from the cutsheet — every other characteristic follows.
| Parameter | What it does | Atlas DC1 TX-A |
|---|---|---|
| kVA rating | Maximum continuous output. Sized at ~110-125% of demand load to allow thermal cycling. | 2,500 kVA |
| Voltage ratings | Primary / secondary nominal voltages. Determines turns ratio and tap settings. | 12,470 / 480Y/277V |
| %Z (impedance) | Per-unit impedance. Lower %Z → higher fault current downstream. Standard values 4.5–7%. | 5.75% |
| Winding configuration | Δ-Y, Y-Y, Δ-Δ, Y-Δ. Determines neutral availability and grounding strategy. | Δ-Y (delta primary, wye secondary, neutral grounded) |
| Cooling class | How heat is removed. ONAN (oil-natural air-natural), ONAF (oil-natural air-forced), KNAN (less-flammable fluid), Dry-type. | KNAN (less-flammable fluid for indoor use) |
| Insulation class | Temperature rise rating. 65°C standard for new equipment. | 65°C rise |
| Tap settings | ±2.5% no-load taps for fine voltage adjustment. 4 taps each side of nominal typical. | ±5% in 2.5% steps |
Standard kVA Sizes
| Class | Standard sizes (kVA) |
|---|---|
| Single-phase | 1, 1.5, 3, 5, 7.5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333, 500 |
| Three-phase | 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500, 3000, 5000, 7500, 10,000 |
Winding Configurations — Δ vs Y
| Configuration | Where used | Pros | Cons |
|---|---|---|---|
| Δ-Y (delta-wye) | Most common. Distribution transformers, all utility step-downs to commercial/industrial | Wye secondary provides neutral for 1φ loads. Delta primary blocks zero-sequence currents from secondary fault → quieter primary. | 30° phase shift between primary and secondary (leading or lagging by 30°, depending on labeling) |
| Y-Y (wye-wye) | Some utility distribution, autotransformers, industrial step-downs where primary and secondary both need neutrals | No phase shift. Both sides have neutrals available. | Requires careful 3rd-harmonic management; ground faults transfer between primary and secondary |
| Δ-Δ (delta-delta) | Industrial 480V-480V step transformers, isolation transformers | No phase shift. Open-delta operation possible (one bank can fail and system continues). | No neutral. Cannot serve 1φ phase-to-neutral loads. |
| Y-Δ (wye-delta) | Step-up transformers (generator to grid), some industrial applications | Generator side has neutral. Delta secondary blocks 3rd harmonics from grid. | 30° phase shift (opposite direction from Δ-Y). |
Why %Z Matters — Fault Current Downstream
%Z (per-unit impedance) determines how much current the transformer can deliver into a downstream fault. Lower %Z = higher fault current. This sets the AIC requirement for downstream switchgear.
Inrush Current — Why Upstream Protection Sees the Pain
When energizing a transformer, the inrush can be 8–12× rated current for the first half-cycle, decaying to normal in 6-10 cycles. Upstream OCPD must allow this without tripping.
| Aspect | Detail |
|---|---|
| Magnitude | 8-12× FLA peak first half-cycle; decays in 6-10 cycles to normal |
| Cause | DC offset in flux when energized — depends on point-on-wave of switching |
| Mitigation | Upstream OCPD picked to coordinate above inrush curve. NEC 450.3 specifies primary protection ≤ 250% of rated primary current for transformers ≥ 1000V. |
| Sympathy inrush | Energizing a new transformer can trigger inrush in already-energized adjacent transformers — must consider in protection coordination |
Worked Example 1 — Atlas DC1 TX-A Sizing & Fault Current
- Why 2,500 kVA? Side A demand was ~2,791 kVA (from §03). 2,500 kVA appears slightly undersized — but real installation oversizes the genset side and accepts brief overload at full IT loading. Many real DCs would spec 3,000 kVA.
- Secondary FLA:FLA = 2,500,000 / (√3 × 480) = 3,007 A
- Fault current at 480V bus (using %Z):Ifault = 3,007 / 0.0575 = 52,300 A symmetric→ 480V SWGR-A bus must be rated for ≥ 52 kA AIC. Standard ratings: 65 kA. ✓
- Inrush: 10× × 3007 = ~30 kA peak first half cycle. Primary breaker (12.47 kV side) must let this through.
- Primary protection (NEC 450.3 for transformers ≥ 1000V): 250% × primary FLA = 2.5 × (2,500,000 / (√3 × 12,470)) = 2.5 × 116 = 290 A. Primary CB sized at 300 A or fuse at 250 A. ✓
Worked Example 2 — Office Building Step-Down (480→208/120V)
- Office demand load: 50 kW lighting + 10 kVA receptacles + 5 kVA misc = ~65 kVA total demand. → Use 75 kVA standard size.
- Primary FLA: 75,000 / (√3 × 480) = 90 A
- Secondary FLA: 75,000 / (√3 × 208) = 208 A
- Primary protection (NEC 450.3(B), < 1000V): 125% of primary FLA → 113 A → use 125 A breaker.
- Secondary protection (NEC 450.3 not required if primary is sized at <125%): Many designs add secondary protection anyway — 225 A panelboard MCB matches the 208 A secondary FLA.
- Fault current at 208V bus: 208 / 0.05 = 4,160 A. 208V panelboards routinely rated for 10 kA AIC — ample margin.
Drill — Quick Self-Check
Work each problem mentally; reveal to check. Goal: reflex, not deliberation.
1,500 kVA, 480V 3φ secondary. FLA?
1,500 kVA, %Z = 5.5%. Approximate fault current at secondary (infinite primary)?
A transformer secondary serves both 3φ motors AND 1φ-N lighting. Configuration?
1,500 kVA at 4160V (primary). NEC 450.3 max primary OCPD?
Atlas TX-A: 2,500 kVA, 480V secondary, %Z = 5.75. Fault at secondary (infinite primary)?
Worked Example 3 — Setting Transformer Taps for Voltage Optimization
Real utility primary voltage often runs slightly off nominal. Distribution transformers have ±2.5% no-load taps to compensate. Setting the tap correctly delivers nominal voltage at the secondary loads.
The problem
- Utility primary measured = 12,830V (2.9% high above 12,470V nominal). Common when transformer is close to substation.
- TX-A secondary with all taps in nominal position would deliver: 12,830 / 12,470 × 480 = 494V at light load.Per ANSI C84.1, utilization range is 456V to 504V (95-105% of 480V). 494V is within range but tight, especially if drops accumulate downstream.
Tap selection
TX-A has 5 no-load primary taps in 2.5% steps: +5%, +2.5%, Nominal, −2.5%, −5%.
- Choose the +2.5% tap. This raises the primary turns by 2.5%, requiring 2.5% more primary voltage to deliver the same secondary voltage.
- New secondary at no-load:Vsec = (12,830 / 12,470) × (1 / 1.025) × 480 = 1.029 × 0.9756 × 480 = 482VCentered in the 456-504V range. Plenty of margin for downstream voltage drops.
If You See THIS, Think THAT
| If you see… | Think / use… |
|---|---|
| "%Z" or "5.75%" on cutsheet | Per-unit impedance. Drives fault current. Lower %Z = more fault current downstream. |
| "Δ-Y" winding | Standard utility/commercial config. 30° phase shift. Wye secondary has neutral. |
| "Y-Y" winding | Both sides have neutrals. Watch for 3rd harmonic issues. Less common. |
| "Δ-Δ" winding | No neutral. Industrial 480-480V isolation. Cannot serve 1φ-N loads from secondary. |
| "K-factor 4" or "K-13" transformer | Designed for harmonic loads (servers, VFDs, LEDs). Larger neutral, special core. Used in DCs. |
| "Pad-mount" transformer | Outdoor utility-grade. 12.47kV/480V typically. Used at service entrance for commercial/industrial. |
| "Dry-type" transformer | Indoor, no oil. NEMA 1 enclosure. Lower %Z = louder. Cooling: AA (ambient air), AFA (forced air). |
| "ONAN/KNAN" transformer | Liquid-cooled. ONAN = mineral oil, KNAN = less-flammable fluid (FM-200, Envirotemp). KNAN is required for indoor liquid-cooled. |
| "Inrush current" | 8-12× rated for ~half cycle. Upstream OCPD must coordinate above inrush curve. NEC 450.3 sizing. |
| NEC 450.3 | Transformer overcurrent protection. ≥ 1000V: ≤ 250% primary; < 1000V: ≤ 125% primary (with exceptions). |
| Tap settings shown | ±2.5% no-load taps. Adjust if utility primary voltage is consistently high or low. |