Protection & Relaying
Breakers are dumb — they trip when current exceeds a setting. Relays are smart — they decide WHEN and WHY. Every protection device has an ANSI device number. Coordination studies plot the curves and verify selectivity.
ANSI/IEEE Device Numbers
Every protective device has a number. The IEEE C37.2 standard assigns 1-99 (some up to 999) to specific functions. Memorize the dozen most-used; the rest are looked up.
| Device # | Function | Where used |
|---|---|---|
| 21 | Distance relay | Transmission line protection |
| 25 | Synchronism check | Generator paralleling, ATS closed-transition |
| 27 | Undervoltage | Motor protection, generator dropout |
| 32 | Reverse power (directional power) | Generator protection (motoring), prevent backfeed |
| 37 | Undercurrent | Motor loss-of-load protection (e.g., loss of cooling) |
| 40 | Loss of field (excitation) | Synchronous motor / generator protection |
| 46 | Negative sequence (current unbalance) | Motor protection — phase loss, unbalanced load |
| 47 | Phase sequence / phase reversal | Verify correct phase rotation on incoming feed |
| 49 | Thermal overload (machine) | Motor + transformer protection |
| 50 | Instantaneous overcurrent | Universal — fastest trip on high faults |
| 51 | Time-overcurrent (inverse-time) | Universal — coordinated overcurrent |
| 50G / 51G | Ground fault (50 = inst, 51 = time) | Detects ground faults; required by NEC 230.95 for large 480V services |
| 50N / 51N | Residual neutral overcurrent | Ground fault on Y-grounded systems |
| 59 | Overvoltage | Generator protection, capacitor protection |
| 67 | Directional overcurrent | Looped systems where fault current can flow either direction |
| 79 | Auto-reclose | Distribution feeder breakers; reclose after temporary fault |
| 81 | Frequency (under or over) | Generator protection, load shedding, intentional islanding |
| 87 | Differential | Transformer (87T), bus (87B), motor (87M), generator (87G) — fastest, most selective protection |
| 87L | Line differential | Transmission line — pilot protection |
Inverse-Time vs Definite-Time vs Instantaneous Tripping
| Tripping characteristic | Description | Where used |
|---|---|---|
| Instantaneous (50) | No intentional delay — trip in < 1 cycle when current exceeds setpoint | High-fault region — clears bolted faults fastest |
| Definite-time (51 with definite-time setting) | Fixed delay regardless of current magnitude (after pickup) | Backup protection — coordinates above downstream device's clearing time |
| Inverse-time (51) | Higher current → faster trip. IEC and IEEE curves: standard inverse, very inverse, extremely inverse | Universal time-overcurrent. Coordinates naturally with downstream OCPDs at all current levels |
| Pickup current | The current threshold that "starts" the timing element | Set above maximum normal load current with margin |
| Time dial | Multiplier on the curve — shifts curve up/down | Coordinated with downstream; lower TD = faster operation |
Differential Protection (87)
Differential measures current entering a zone vs current leaving. If they don't match, current is going somewhere it shouldn't — internal fault. Trips immediately. The fastest protection available, with no coordination delay needed because it only operates on faults INSIDE its protection zone.
| Differential type | Protected zone | Operation |
|---|---|---|
| 87T Transformer differential | Inside the transformer windings | CTs on primary + secondary. Compensates for turns ratio + winding configuration. Trips on any internal fault. |
| 87B Bus differential | Inside the switchgear bus | CTs on every bus connection. Sum should be zero. Trips on any bus fault — clears in < 1 cycle, prevents catastrophic arc flash. |
| 87M Motor differential | Inside the motor windings | CTs on phase + neutral connections. Detects winding-to-winding fault. |
| 87G Generator differential | Inside generator windings | Same principle — most generators have 87G as primary protection. |
| 87L Line differential (pilot) | Transmission line | Communication channel between line ends compares currents. Telecomm-dependent. |
Modern Numerical Relays
Old-school electromechanical relays (cup-and-disk) are being replaced everywhere by numerical relays — microprocessor-based devices that combine many ANSI functions in one box, with communication, event logging, and remote access.
| Manufacturer | Common product line | Notes |
|---|---|---|
| Schweitzer Engineering Labs (SEL) | SEL-351, 387, 411, 421, 487 | Industry leader. Strong cybersecurity. Engineering-friendly programming. |
| GE / Multilin | F60, F35, MIF II, T60 | Strong utility presence. UR family. |
| ABB | Relion 615, 620, 630, 670 series | European-strong; 60870-5-103/104 native. |
| Siemens | SIPROTEC 4 / 5 | European-strong; integrated DIGSI software. |
| Eaton | EDR 5000, MP-3000, MP-4000 | Industrial focus. |
Coordination Study — The Deliverable
A coordination study plots every TCC for every OCPD on a single log-log chart, with the available fault current marked. The result: visual confirmation that for any fault, only the closest device opens.
| Component | What's shown |
|---|---|
| Source impedance line | Available fault current at each bus |
| OCPD curves | Each device's TCC at its protected location |
| Cable damage curve | Conductor I²t damage threshold (NEC 110.10) |
| Transformer damage curve | Per IEEE C57.109 / ANSI |
| Motor inrush region | For motor branches, plot inrush curve to ensure CB doesn't trip on starting |
| Selectivity bands | Time gap between upstream and downstream curves (≥ 0.3 sec typical for fuses, ≥ 0.4 sec for CBs) |
Worked Example 1 — Atlas DC1 MV Switchgear Protection Scheme
Protection functions on each device
| Position | Protection (ANSI #s) | Why |
|---|---|---|
| Utility incoming CB (12.47 kV) | 50, 51, 50G, 51G, 27, 59, 81 | Standard incoming protection: overcurrent, ground, voltage, frequency |
| TX-A primary CB (12.47 kV) | 87T (with TX-A secondary CT input), 50, 51, 50G, 51G, 26 (sudden gas pressure) | Differential primary protection of TX-A — trips on any internal fault. Backup overcurrent. |
| TX-A secondary CB (480V) | 50, 51, 50G, 51G, GFP per NEC 230.95 | Backup feeder protection for 480V SWGR |
| Bus differential 87B | One zone per side (A bus and B bus) | Clears bus fault in < 1 cycle — minimizes arc flash |
Why each device matters
- 87T transformer differential: A winding-to-winding fault inside TX-A would draw fault current from utility but the fault location is inside the transformer enclosure. Without 87T, only the slower 51 element trips → significant transformer damage. With 87T, trip in 1-2 cycles.
- 87B bus differential: A fault on the 480V bus (e.g., insulation failure from a falling tool) would otherwise wait for transformer 51 to time out (~ 100 ms+). At 50 kA fault current, that's massive incident energy. 87B clears in 4 cycles → 90% reduction in incident energy.
- 50G/51G ground fault: Detects ground faults on solidly-grounded system before they escalate to phase-phase faults. Sensitivity: 100-1200 A typical setting.
Worked Example 2 — Industrial Motor Protection (49, 51, 46, 27)
| ANSI # | Function | Setting | Why |
|---|---|---|---|
| 49 | Thermal overload | Per NEC 430.32 — 115% of FLA for SF=1.0; 125% for SF=1.15 | Protect motor windings from thermal damage |
| 50 | Instantaneous OC | ~ 130% of locked-rotor | Bolted fault on motor leads |
| 51 | Time-OC | 120-130% FLA pickup, time dial coordinates with upstream | Backup to thermal overload |
| 46 | Negative sequence | Pickup at ~ 5% I2/I1 | Detects phase loss and unbalance — both very damaging to induction motors |
| 27 | Undervoltage | ~ 80% of nominal | Drop motor on sustained undervoltage to prevent stall and overheating |
| 37 | Undercurrent | Custom per application | Optional — detect loss of load (broken pump shaft, etc.) |
One numerical relay (e.g., SEL-710) provides all of these functions plus event recording and Modbus communication. Old electromechanical equivalent would be 4-6 separate panels.
Coordination Plot Example — Atlas DC1 MV Protection
The TCC plot for the MV switchgear protection chain: utility 51 → TX-A primary 51 + 87T → 480V SWGR-A 51 + 87B.
Drill — Quick Self-Check
Work each problem mentally; reveal to check. Goal: reflex, not deliberation.
What are 50, 51, 87?
Why is 87T (transformer differential) faster than 51?
Two settings on a 51 element?
What does 46 detect?
What protection does Atlas DC1's MV switchgear use?
Instrument Transformers — CT + PT
Protective relays and meters can't measure thousands of amps or thousands of volts directly. CTs and PTs step these down to safe, standardized values (5 A and 120 V respectively).
Current Transformers (CTs)
| Parameter | Description |
|---|---|
| Ratio | Primary:secondary, e.g., 1200:5 means 1200 A primary → 5 A secondary at full load |
| Burden | Load on the secondary (relays + wiring + meters). Specified in VA. Higher burden = more saturation risk. |
| Accuracy class | For metering: 0.3, 0.6, 1.2 (% error at rated burden). For relaying: C100, C200, C400, C800 (relaying class — voltage at saturation). |
| Polarity | Marked terminals (H1 + X1). Critical for differential protection — wrong polarity = immediate trip on energization. |
| Saturation | At very high primary current (faults), CT iron core saturates → secondary output stops following primary. Causes incorrect relay operation. Sized to avoid saturation at maximum fault current. |
| Open secondary danger | Never open a CT secondary while energized! With no burden, voltage rises to thousands of volts → arcing + insulation failure + lethal. Always short-circuit before disconnecting. |
Potential Transformers (PTs / VTs)
| Parameter | Description |
|---|---|
| Ratio | Primary:secondary, e.g., 14400:120 means 14.4 kV primary → 120 V secondary |
| Burden | Same concept as CT but secondary is voltage-limited not current-limited |
| Accuracy class | 0.3, 0.6, 1.2 metering. Various relaying classes. |
| Connection types | Wye-wye (most common), open-delta, V-V (used when delta primary system has no available neutral) |
| Capacitive Voltage Transformers (CVTs) | Used at very high voltages (≥ 138 kV) — capacitive divider + tuning circuit. Cheaper than full magnetic PT. |
Ladder Logic — Relay Programming Basics
Ladder logic is a graphical programming language designed to mimic the wiring diagrams of relay-based control panels. PLCs use it; modern protective relays often use a similar logic syntax.
| Symbol | Meaning |
|---|---|
--| |-- | Normally open contact (input). True when input is energized. |
--|/|-- | Normally closed contact (input). True when input is NOT energized. |
--( )-- | Output coil. Energized when the rung's logic is true. |
--(L)-- | Latching output coil. Stays energized after one true cycle. |
--(U)-- | Unlatching coil. Resets a latched output. |
| Rungs in series | AND logic — all conditions must be true |
| Rungs in parallel | OR logic — any condition true energizes output |
Boolean Algebra — The Math Behind Ladder
| Operation | Symbol | Truth | Ladder equivalent |
|---|---|---|---|
| AND | · or & | 1·1 = 1; else 0 | Series contacts |
| OR | + or | | 0+0 = 0; else 1 | Parallel contacts |
| NOT | Bar over var | NOT(0) = 1; NOT(1) = 0 | Normally-closed contact |
| NAND | NOT(AND) | NOT(1·1) = 0; else 1 | Series of NC contacts |
| NOR | NOT(OR) | NOT(0+0) = 1; else 0 | Parallel of NC contacts |
| XOR | ⊕ | 1 if exactly one input is 1 | (A·NOT B) + (NOT A·B) |
If You See THIS, Think THAT
| If you see… | Think / use… |
|---|---|
| "51" | Time-overcurrent. Universal coordinated protection. |
| "50" | Instantaneous OC. Fastest trip on high fault. |
| "87T" | Transformer differential. Internal-fault protection. Sub-cycle clearing. |
| "87B" | Bus differential. Critical for arc flash reduction. |
| "50G", "51G" | Ground fault elements. NEC 230.95 requires for 480V services ≥ 1000A. |
| "49" thermal overload | Motor protection. NEC 430.32 sets the limits. |
| "46" negative sequence | Detects phase loss / unbalance on motors. Very valuable — prevents motor damage from single-phasing. |
| "27" undervoltage | Motor protection (drop on UV) or generator protection. |
| "81" frequency | Generator protection or load shedding logic. |
| "25" synchronism check | ATS closed-transition. Generator paralleling. |
| SEL-351 / SEL-787 / SEL-787-3 | Schweitzer relays — feeder, transformer, multi-phase. Industry standard for new installations. |
| "Coordination study" | Plot of all TCCs. Verify selectivity at all fault levels. |
| "Pickup" + "time dial" | The two settings on every 51 element. |