PART VI Advanced Protection
§18 / 39

Protection & Relaying

ANSI device numbers · 51/50/87/27/49 · differential · numerical relays

Breakers are dumb — they trip when current exceeds a setting. Relays are smart — they decide WHEN and WHY. Every protection device has an ANSI device number. Coordination studies plot the curves and verify selectivity.

ANSI/IEEE Device Numbers

Every protective device has a number. The IEEE C37.2 standard assigns 1-99 (some up to 999) to specific functions. Memorize the dozen most-used; the rest are looked up.

Device #FunctionWhere used
21Distance relayTransmission line protection
25Synchronism checkGenerator paralleling, ATS closed-transition
27UndervoltageMotor protection, generator dropout
32Reverse power (directional power)Generator protection (motoring), prevent backfeed
37UndercurrentMotor loss-of-load protection (e.g., loss of cooling)
40Loss of field (excitation)Synchronous motor / generator protection
46Negative sequence (current unbalance)Motor protection — phase loss, unbalanced load
47Phase sequence / phase reversalVerify correct phase rotation on incoming feed
49Thermal overload (machine)Motor + transformer protection
50Instantaneous overcurrentUniversal — fastest trip on high faults
51Time-overcurrent (inverse-time)Universal — coordinated overcurrent
50G / 51GGround fault (50 = inst, 51 = time)Detects ground faults; required by NEC 230.95 for large 480V services
50N / 51NResidual neutral overcurrentGround fault on Y-grounded systems
59OvervoltageGenerator protection, capacitor protection
67Directional overcurrentLooped systems where fault current can flow either direction
79Auto-recloseDistribution feeder breakers; reclose after temporary fault
81Frequency (under or over)Generator protection, load shedding, intentional islanding
87DifferentialTransformer (87T), bus (87B), motor (87M), generator (87G) — fastest, most selective protection
87LLine differentialTransmission line — pilot protection

Inverse-Time vs Definite-Time vs Instantaneous Tripping

Tripping characteristicDescriptionWhere used
Instantaneous (50)No intentional delay — trip in < 1 cycle when current exceeds setpointHigh-fault region — clears bolted faults fastest
Definite-time (51 with definite-time setting)Fixed delay regardless of current magnitude (after pickup)Backup protection — coordinates above downstream device's clearing time
Inverse-time (51)Higher current → faster trip. IEC and IEEE curves: standard inverse, very inverse, extremely inverseUniversal time-overcurrent. Coordinates naturally with downstream OCPDs at all current levels
Pickup currentThe current threshold that "starts" the timing elementSet above maximum normal load current with margin
Time dialMultiplier on the curve — shifts curve up/downCoordinated with downstream; lower TD = faster operation

Differential Protection (87)

Differential measures current entering a zone vs current leaving. If they don't match, current is going somewhere it shouldn't — internal fault. Trips immediately. The fastest protection available, with no coordination delay needed because it only operates on faults INSIDE its protection zone.

Differential typeProtected zoneOperation
87T Transformer differentialInside the transformer windingsCTs on primary + secondary. Compensates for turns ratio + winding configuration. Trips on any internal fault.
87B Bus differentialInside the switchgear busCTs on every bus connection. Sum should be zero. Trips on any bus fault — clears in < 1 cycle, prevents catastrophic arc flash.
87M Motor differentialInside the motor windingsCTs on phase + neutral connections. Detects winding-to-winding fault.
87G Generator differentialInside generator windingsSame principle — most generators have 87G as primary protection.
87L Line differential (pilot)Transmission lineCommunication channel between line ends compares currents. Telecomm-dependent.

Modern Numerical Relays

Old-school electromechanical relays (cup-and-disk) are being replaced everywhere by numerical relays — microprocessor-based devices that combine many ANSI functions in one box, with communication, event logging, and remote access.

ManufacturerCommon product lineNotes
Schweitzer Engineering Labs (SEL)SEL-351, 387, 411, 421, 487Industry leader. Strong cybersecurity. Engineering-friendly programming.
GE / MultilinF60, F35, MIF II, T60Strong utility presence. UR family.
ABBRelion 615, 620, 630, 670 seriesEuropean-strong; 60870-5-103/104 native.
SiemensSIPROTEC 4 / 5European-strong; integrated DIGSI software.
EatonEDR 5000, MP-3000, MP-4000Industrial focus.

Coordination Study — The Deliverable

A coordination study plots every TCC for every OCPD on a single log-log chart, with the available fault current marked. The result: visual confirmation that for any fault, only the closest device opens.

ComponentWhat's shown
Source impedance lineAvailable fault current at each bus
OCPD curvesEach device's TCC at its protected location
Cable damage curveConductor I²t damage threshold (NEC 110.10)
Transformer damage curvePer IEEE C57.109 / ANSI
Motor inrush regionFor motor branches, plot inrush curve to ensure CB doesn't trip on starting
Selectivity bandsTime gap between upstream and downstream curves (≥ 0.3 sec typical for fuses, ≥ 0.4 sec for CBs)

Worked Example 1 — Atlas DC1 MV Switchgear Protection Scheme

Example 01 · Atlas DC1 spine12.47 kV switchgear protecting TX-A and TX-B + utility incoming

Protection functions on each device

PositionProtection (ANSI #s)Why
Utility incoming CB (12.47 kV)50, 51, 50G, 51G, 27, 59, 81Standard incoming protection: overcurrent, ground, voltage, frequency
TX-A primary CB (12.47 kV)87T (with TX-A secondary CT input), 50, 51, 50G, 51G, 26 (sudden gas pressure)Differential primary protection of TX-A — trips on any internal fault. Backup overcurrent.
TX-A secondary CB (480V)50, 51, 50G, 51G, GFP per NEC 230.95Backup feeder protection for 480V SWGR
Bus differential 87BOne zone per side (A bus and B bus)Clears bus fault in < 1 cycle — minimizes arc flash

Why each device matters

  1. 87T transformer differential: A winding-to-winding fault inside TX-A would draw fault current from utility but the fault location is inside the transformer enclosure. Without 87T, only the slower 51 element trips → significant transformer damage. With 87T, trip in 1-2 cycles.
  2. 87B bus differential: A fault on the 480V bus (e.g., insulation failure from a falling tool) would otherwise wait for transformer 51 to time out (~ 100 ms+). At 50 kA fault current, that's massive incident energy. 87B clears in 4 cycles → 90% reduction in incident energy.
  3. 50G/51G ground fault: Detects ground faults on solidly-grounded system before they escalate to phase-phase faults. Sensitivity: 100-1200 A typical setting.
i
Why DCs invest heavily in protection
A typical commercial building's MV switchgear has 51 and 50G — that's it. Atlas DC1 adds 87T, 87B, 27, 59, 81 because every cycle of clearing time matters: less arc flash, less downtime, less chance of cascading failure into the IT load. The cost is justified by the value at stake.

Worked Example 2 — Industrial Motor Protection (49, 51, 46, 27)

Example 02 · Alternate context500 HP induction motor on 480V — protected by integrated motor relay
ANSI #FunctionSettingWhy
49Thermal overloadPer NEC 430.32 — 115% of FLA for SF=1.0; 125% for SF=1.15Protect motor windings from thermal damage
50Instantaneous OC~ 130% of locked-rotorBolted fault on motor leads
51Time-OC120-130% FLA pickup, time dial coordinates with upstreamBackup to thermal overload
46Negative sequencePickup at ~ 5% I2/I1Detects phase loss and unbalance — both very damaging to induction motors
27Undervoltage~ 80% of nominalDrop motor on sustained undervoltage to prevent stall and overheating
37UndercurrentCustom per applicationOptional — detect loss of load (broken pump shaft, etc.)

One numerical relay (e.g., SEL-710) provides all of these functions plus event recording and Modbus communication. Old electromechanical equivalent would be 4-6 separate panels.

Coordination Plot Example — Atlas DC1 MV Protection

The TCC plot for the MV switchgear protection chain: utility 51 → TX-A primary 51 + 87T → 480V SWGR-A 51 + 87B.

100 1k 10k 100k Current (A at 12.47 kV) — log 100s 10s 1s 0.1s 0.01s 480V SWGR 51 87B (4 cycles) TX-A primary 51 87T (1-2 cycles) Utility 51 (backup) 50 kA fault PROTECTION SEQUENCE Bus fault @ 480V SWGR: 87B trips → 67 ms (best) Internal fault @ TX-A: 87T trips → 33 ms (best) Backup if 87 fails: TX 51 → 200-300 ms Last resort: Utility 51 → 500+ ms
Differential (87B, 87T) clears INSIDE its zone faster than any 51 element — sub-cycle vs hundreds of milliseconds. Critical for arc flash.

Drill — Quick Self-Check

Work each problem mentally; reveal to check. Goal: reflex, not deliberation.

Drill 1 · Top ANSI numbers

What are 50, 51, 87?

Drill 2 · 87T speed

Why is 87T (transformer differential) faster than 51?

Drill 3 · Pickup vs time dial

Two settings on a 51 element?

Drill 4 · Negative sequence (46)

What does 46 detect?

Drill 5 · Atlas MV

What protection does Atlas DC1's MV switchgear use?

Instrument Transformers — CT + PT

Protective relays and meters can't measure thousands of amps or thousands of volts directly. CTs and PTs step these down to safe, standardized values (5 A and 120 V respectively).

Current Transformers (CTs)

ParameterDescription
RatioPrimary:secondary, e.g., 1200:5 means 1200 A primary → 5 A secondary at full load
BurdenLoad on the secondary (relays + wiring + meters). Specified in VA. Higher burden = more saturation risk.
Accuracy classFor metering: 0.3, 0.6, 1.2 (% error at rated burden). For relaying: C100, C200, C400, C800 (relaying class — voltage at saturation).
PolarityMarked terminals (H1 + X1). Critical for differential protection — wrong polarity = immediate trip on energization.
SaturationAt very high primary current (faults), CT iron core saturates → secondary output stops following primary. Causes incorrect relay operation. Sized to avoid saturation at maximum fault current.
Open secondary dangerNever open a CT secondary while energized! With no burden, voltage rises to thousands of volts → arcing + insulation failure + lethal. Always short-circuit before disconnecting.

Potential Transformers (PTs / VTs)

ParameterDescription
RatioPrimary:secondary, e.g., 14400:120 means 14.4 kV primary → 120 V secondary
BurdenSame concept as CT but secondary is voltage-limited not current-limited
Accuracy class0.3, 0.6, 1.2 metering. Various relaying classes.
Connection typesWye-wye (most common), open-delta, V-V (used when delta primary system has no available neutral)
Capacitive Voltage Transformers (CVTs)Used at very high voltages (≥ 138 kV) — capacitive divider + tuning circuit. Cheaper than full magnetic PT.

Ladder Logic — Relay Programming Basics

Ladder logic is a graphical programming language designed to mimic the wiring diagrams of relay-based control panels. PLCs use it; modern protective relays often use a similar logic syntax.

SymbolMeaning
--| |--Normally open contact (input). True when input is energized.
--|/|--Normally closed contact (input). True when input is NOT energized.
--( )--Output coil. Energized when the rung's logic is true.
--(L)--Latching output coil. Stays energized after one true cycle.
--(U)--Unlatching coil. Resets a latched output.
Rungs in seriesAND logic — all conditions must be true
Rungs in parallelOR logic — any condition true energizes output

Boolean Algebra — The Math Behind Ladder

OperationSymbolTruthLadder equivalent
AND· or &1·1 = 1; else 0Series contacts
OR+ or |0+0 = 0; else 1Parallel contacts
NOTBar over varNOT(0) = 1; NOT(1) = 0Normally-closed contact
NANDNOT(AND)NOT(1·1) = 0; else 1Series of NC contacts
NORNOT(OR)NOT(0+0) = 1; else 0Parallel of NC contacts
XOR1 if exactly one input is 1(A·NOT B) + (NOT A·B)

If You See THIS, Think THAT

If you see…Think / use…
"51"Time-overcurrent. Universal coordinated protection.
"50"Instantaneous OC. Fastest trip on high fault.
"87T"Transformer differential. Internal-fault protection. Sub-cycle clearing.
"87B"Bus differential. Critical for arc flash reduction.
"50G", "51G"Ground fault elements. NEC 230.95 requires for 480V services ≥ 1000A.
"49" thermal overloadMotor protection. NEC 430.32 sets the limits.
"46" negative sequenceDetects phase loss / unbalance on motors. Very valuable — prevents motor damage from single-phasing.
"27" undervoltageMotor protection (drop on UV) or generator protection.
"81" frequencyGenerator protection or load shedding logic.
"25" synchronism checkATS closed-transition. Generator paralleling.
SEL-351 / SEL-787 / SEL-787-3Schweitzer relays — feeder, transformer, multi-phase. Industry standard for new installations.
"Coordination study"Plot of all TCCs. Verify selectivity at all fault levels.
"Pickup" + "time dial"The two settings on every 51 element.