An Electrical Design Handbook

Power Atlas

Every concept in electrical design — from the master equipment list to arc flash labels — taught through one reference facility you carry from start to finish.

Sections
39
comprehensive chapters
Spine
DC1
2.5 MW · Tier III
Examples
64
2 worked per section
Begin → Section 00 Browse all sections
⚡ Theory Primer 📐 Atlas DC1 Specs 🏢 DC Tiers 🗺 Connection Map 📖 Glossary 🖨 Print / PDF
The Reference Facility
Atlas DC1 — One-Line Diagram
2N · Tier III
UTILITY SOURCE 12.47 kV · 3φ · 60 Hz Δ MV SWGR · 12.47 kV TX-A 2500 kVA · 12.47kV–480Y/277V %Z = 5.75 TX-B 2500 kVA · 12.47kV–480Y/277V %Z = 5.75 GEN GEN-A 2500 kW · 480V · diesel GEN GEN-B 2500 kW · 480V · diesel ATS ATS-A ATS ATS-B 480V SWGR — A · 4000A bus 480V SWGR — B · 4000A bus N.O. tie UPS ~/=/~ UPS-A1 · 1250 kVA UPS ~/=/~ UPS-A2 · 1250 kVA M CH-1 · 750T FLA 480A M CH-2 · 750T FLA 480A UPS ~/=/~ UPS-B1 · 1250 kVA UPS ~/=/~ UPS-B2 · 1250 kVA M CH-3 · 750T FLA 480A M CH-4 · 750T FLA 480A UPS BUS A · 415Y/240V UPS BUS B · 415Y/240V IT ROW A · 1.25 MW IT ROW B · 1.25 MW
MV bus 480V UPS Fully detailed in §02